Product

LVAF series low voltage active harmonic filter

        LVAF active power filter is a new power electronic device of dynamically suppressing harmonics, reactive power compensation, through real-time detection of the load current waveform and DSP calculation, to obtain content of load current harmonic, then a PWM signal to inverter controlled by IGBT, such, to produce a current as big as load harmonic current but opposite direction into power supply system. Finally, the harmonic is filtered.

Introduction

  • LVAF active power filter is a new power electronic device of dynamically suppressing harmonics, reactive power compensation, through real-time detection of the load current waveform and DSP calculation, to obtain content of load current harmonic, then a PWM signal to inverter controlled by IGBT, such, to produce a current as big as load harmonic current but opposite direction into power supply system. Finally, the harmonic is filtered.

Main Parameter

Rated voltage: 0.4kV
Frequency: 45Hz ~ 63Hz
Efficiency: 97%
Filtering capacity: THDi (current distortion rate) < 5%
Response time: less than 15ms
Communication interface: RS485, network port
Communication protocol: the power of the general protocol, Modbus protocol, TCP/IP
Protection grade: IP20, the remaining IP grade can be customized

Feature

  • Compact and reasonable structure, flexible installation.
  • Advanced control algorithm, software reliability.
  • Double DSP control system, using vector screening technology.
  • Dynamic filter 2 to 50 harmonics, may optionally specified harmonic filter.
  • Harmonic compensation, reactive power compensation and three-phase unbalance compensation.
  • Various capacity module, arbitrary combination and capacity expansion machine, good performance, to meet the different needs of the system capacity.
  • Standard communication interface and communication protocol.
  • Fault alarm and recording function, can be as much as 500 alarm records.
  • With all kinds of complete and effective protection measures, such as over-voltage protection, under voltage protection, short circuit protection, inverter bridge reverse protection, compensation protection etc.
  • Load change process, if the resonance, APFM self judgment and exit system, at the same time, alarm, and avoid

Model Guide

auto power factor correction.jpg  

Standards

  • GB/T 14549-1993
  • JB/T 11067-2011

  • Primary Electrical Diagram

    diagram.jpg  

Model Selection Guide

  • The rated voltage and rated capacity of the device should be reflected in the order model, and other special requirements must be noted;
  • LVAF series active filters have two structural modes: integrated cabinet type and modular combined cabinet type, which can be combined with all mainstream switch cabinets of low voltage, and are suitable for different busbar fixing positions and methods;
  • The device configuration and structure size can be negotiated according to user requirements.
  • Cabinet size requirements, environmental conditions and protection level of the installation site
  • Required power factor and harmonic distortion rate and other requirements

Example:

  • If the rated voltage of a system is 0.4kV and 200A harmonic current needs to be filtered out, it is recommended to use an active filter device of model LVAF-0.4-200, which adopts an integrated cabinet structure, consisting of a cabinet with a size of 800 ×1000×2200mm, or use an active filter device of model LVAF-0.4-200/2, use a 100A module, and consist of a cabinet with a size of 600×1000×2200mm.

Online